Friday, April 12, 2013

Fact Sheet: 2011 Combustible Dust Related Incidents, NFIRS Analysis


Fact Sheet: 2011 Combustible Dust Related Incidents, NFIRS Analysis from Combustible Dust Policy Institute



A Combustible Dust Policy Institute (CDPI) preliminary analysis of 2011 National Fire Incident Reporting System (NFIRS) incident data provided by the National Fire Data Center of the U.S. Fire Administration indicated over 500 combustible dust related incidents in manufacturing facilities where dust was the item first ignited. Near misses include incidents that did not result in any harm to personnel, the facility, process, or product. Analysis did not include the grain sector or coal-fired energy plants.

Additionally, the CDPI analysis does not include many incidents that were not reported by fire departments to the National Fire Data Center. As a result there are many more combustible dust related incidents that cannot be evaluated in determining whether the incident was a near miss or not. 

Special thanks to the nation's Fire Departments, NFIC State Program Managers, and the National Fire Data Center at the U.S. Fire Administration in sharing this valuable Information.  

Casual Pathways Between Near Misses and Catastrophic Events 
Excellent article by Carsten Busch from Norway, highlighting Common Cause Hypothesis (CCH) which also pertains to near misses and catastrophic combustible dust related incidents. In the current OSHA ComDust rulemaking process and recently reintroduced proposed combustible dust bill H.R. 691, incidents resulting in property/content loss (30% NFIRS analysis) yet no casualties (approximately 95%) are considered near misses. Yet the casual pathways (ignition sources, dust management strategies, etc.) for the consequences of all combustible dust related incidents are all the same. 

The true definition of a "near miss" is an incident not resulting in any harm to personnel, the facility, process, or product. So why are near misses ignored in accounting for combustible dust related fire and explosion hazards in protection of the workplace in the OSHA ComDust rulemaking process and recently reintroduced proposed combustible dust bill H.R. 691?

Report on preliminary findings of a study of incident reporting systems for near misses in non­medical domains. This can also apply to combustible dust related incidents/accidents where NFIRS data provides a multitude of information in developing barriers for the prevention of future accidents.

Near Misses in Non­-medical Domains
"Consequently, the same patterns of causes of failure and their relations precede both adverse events and near misses." Sounds familiar with ComDust related incidents at facilities whether it was flash fire, dust explosion, or layer fire? They all have casual pathways of improperly managed ignition sources and fuel sources. A written fire prevention plan (FPP) addresses these casual pathways initially at the organizational level. The next step would be implementation at the technical and operational level.

"We defined a near miss as any event that could have had adverse consequences but did not and was indistinguishable from fully fledged adverse events in all but outcome." Note: National Fire Incident Reporting System (NFIRS) was not included in the report of near misses in non­medical domains. 

U.S. Chemical Safety Board (CSB): Near Misses.
Dust Explosion Hazard Awareness / Imperial Sugar Management and Workers
(Page 54 .pdf) "The CSB concluded that the small events and “near-misses” caused company management, and the managers and workers at both the Port Wentworth, Georgia, and Gramercy, Louisiana, facilities to lose sight of the ongoing and significant hazards posed by accumulated sugar dust in the packing buildings."

CSB Key Findings: Imperial Sugar Refinery
Page 48 .pdf)  # 4 "Company management and the managers and workers at both the Port Wentworth, Georgia, and Gramercy, Louisiana, refineries did not recognize the significant hazard posed by sugar dust, despite the continuing history of “near-misses’”

Hoeganaes
(Page 14 ,pdf) "Operators and mechanics reported being involved in multiple flash fires during their employment at the Gallatin facility. At the time of the incidents, many were aware that the iron dust could burn or smolder. However, they were not trained to understand the potentially severe hazard when accumulated dust is dispersed in air. Rarely would operators report the minor flash fires and “near-misses” that periodically occurred."

(page 27 .pdf) CSB Recommendations to Hoeganaes 2011-4-I-TN-R9
"Develop and implement a “near-miss” reporting and investigation policy that includes the following at a minimum:"
• Ensure facility-wide worker participation in reporting all near-miss events and operational disruptions (such as significant iron powder accumulations, smoldering fires, or unsafe conditions or practices) that could result in worker injury.

• Ensure that the near-miss reporting program requires prompt investigations, as appropriate, and that results are promptly circulated throughout the Hoeganaes Corp.

• Establish roles and responsibilities for the management, execution, and resolution of all recommendations from near-miss investigations

• Ensure the near-miss program is operational at all times (e.g. nights, weekends, holiday shifts).  

Conclusion 
Near misses can no longer be ignored. It's very distressing that OSHA in the combustible dust rulemaking process in conjunction with the legislators in the reintroduction of the proposed combustible dust bill H.R. 691 have chosen to ignore 95% of combustible dust related incidents in manufacturing facilities, which do not result in personnel casualties. Yet these very same incidents, as history illustrates are precursors to catastrophe. 

 

Tuesday, April 2, 2013

Explosion Relief Systems Free AIA Webinar May 1st



“Explosion Relief Systems for Low Strength Enclosures”
Date : Wednesday the 1tst of May 2013 @ 11am EST



C/S Explovent, a division of C/S Construction Specialties, is inviting you to join a free webinar about “Explosion relief systems for low strength enclosures”!



Introduction:

The issue of venting violent overpressures is a critical one for owners of facilities where potentially explosive atmospheres, materials, and processes exist including combustible dust. Recent statistics indicate that the average damage due to explosions in industrial establishments is approximately $3.4 million, compared to $210,000 for  an average fire. The possibility of an explosion occurring must be seen as a real concern considering only three common elements must be in place for an event to occur: ignition source, a fuel, and confinement.  As obvious as it sounds, even fine dust particles and a spark can create an explosive atmosphere.  We might not think of this, but if something can burn, it can likely explode.  




An explosion vent is designed to be the weakest part of the external structure. As the explosion vent experiences the pressure rise, it opens quickly allowing the rapidly expanding heated gases to be released to the outside. By doing so, the internal walls, floor, and ceiling are spared from the damaging overpressure experienced during a deflagration.



To successfully limit damage to the vented area, vent design and the pressure resistant structure must be in keeping with guideline authority recommendations. As such, C/S Explovent® explosion relief systems have been designed in accordance with the NFPA 68 Venting of Deflagrations guideline and Factory Mutual 1-44 Damage Limiting Construction document. Explovent® has been tested, approved, and labelled by Factory Mutual and tested and approved by the Canadian Center for Mineral and Energy Technology for explosion relief applications.
 

Participants will learn:

  • What explosion relief is
  • What industries have a true need for explosion venting products
  • Types of explosions & catalysts as they relate to the industry
  • Why explosion venting should be specified
  • Code drivers & their impact on today's specifiers
  • Overview of available explosion venting products
To register and get more details about this free webinar, just click on the link and follow the step!






About C/S Construction Specialties:
For 60 years, Construction Specialties has been a leader in architectural specialty products, including : Acrovyn® Wall and Door Protection, Pedisystems® Entrance Flooring, Expansion Joint Covers, Cubicle Track and Curtains, Smoke and Explosion Venting Systems, Architectural Grilles, Architectural Louvers and Sun Controls.  We have operations throughout the world and can provide C/S Products virtually anywhere. For a complete list of our international locations, visit www.c-sgroup.com.
This presentation is AIA Accredited










·

·

·        

·     






 


Thursday, March 28, 2013

California Lower Rate of Combustible Dust Related Incidents Due to FPP?


How come California with more manufacturing facilities than any other state (approx. 40,000 establishments-U.S. Census Bureau-2010) yet has a lower rate of combustible dust related incidents than any other state? Could it be that they require fire prevention plans (FPP) for all facilities whereas other states don't? Shouldn't a state with the highest number of facilities also have the highest number of incidents? Quite interesting accidentally connecting the dots between combustible dust related incidents in a preliminary analysis of 2011 NFIRS data and fire prevention plans (FPP) 29 CFR 1910.39.

It’s back to school for us all after coming across this helpful resource with the University of California Riverside's Fire Prevention Plan (FPP) providing an excellent framework with FPP key elements as required by the California Code of Regulations (CCR) Title 8, Section 3221. The detailed FPP document includes a section on Fire Extinguishers where "all faculty and staff are annually provided the opportunity to receive hands-on training and experience in using portable fire extinguishers."

California is one of the approved State Plan States that went beyond minimum federal OSHA regulatory requirements concerning FPP's (Exemptions. 1910.157(b)(1))  For example, California facilities not requiring the immediate and total evacuation of employees from the workplace upon the sounding of a fire alarm signal are required to have a Fire Prevention Plan (CCR Title 8, Section 3221).

Whereas Federal OSHA states don’t require a Fire Prevention Plan (FPP) in this scenario unless the facility follows under one of these three host standards: Ethylene Oxide, 1910.104, Methylenedianiline, 1910.1050, and 1,3 Butadiene, 1910.105. Additionally FPP required where the written fire safety policy requiring the immediate and total evacuation of employees from the workplace upon the sounding of a fire alarm signal.

With a bit of imagination the University of California Riverside's Fire Prevention Plan (FPP) provides an excellent framework for a voluntary FPP’s which should include controlling ignition and fuel sources in the prevention of combustible dust fires and explosions. The U.S. Chemical Safety Board (CSB) did not make any FPP recommendations in the 2006 Dust Hazard Study. As a result OSHA has not recognized FPP in the 2008 Combustible Dust National Emphasis Program (NEP), 2009 Combustible Dust Advanced Notice of Proposed Rulemaking, 2011 OSHA Combustible Dust Expert Forum, nor on the OSHA Combustible Dust Hazards webpage. The Democrat Committee Education and the Workforce has acknowledged this error with the reintroduction of the proposed bill, "H.R. 691 Worker Protection Against Combustible Dust Explosions and Fires in the Workplace," where 40% of the requirements in the bill are from content in the OSHA Fire Prevention Plan (FPP) 29 CFR 1910.39.

Fire prevention plans (FPP) are an excellent administrative and procedural control measure in minimizing the probability of occurrence of future combustible dust related incidents by managing and controlling potential ignition and fuel sources. Without FPP's  combustible dust related incidents will continue to occur in an unabated manner. The majority of combustible dust related incidents are "near misses" precursors to catastrophe. As a result combustible dust hazards are primarily a fire issue and secondarily a potential explosion problem.

Monday, March 25, 2013

Proposed Combustible Dust Bill Relationship to OSHA Regulations

Proposed Combustible Dust Legislation H.R. 691,Worker Protection Against Combustible Dust Explosions and Fires Act of 2013. Presentation illustrates relationship of proposed combustible dust bill with OSHA regulations. Approximately 40% of the requirements are mirrored from content in the OSHA Fire Prevention Plan 1910.39 in addition to approximately 50% of content analogous to OSHA's Process Safety Management 1910.119 regulations.



Many of the NFPA combustible dust standards also include elements of Process Safety Management (PSM) such as management of change (MOC), accident investigations, contractor training, etc. Additionally elements in the requirements of the proposed bill include: Hazard Assessment 1910.132, Hazard Communication (HazCom) 1910.1200, Process Safety Management (PSM) 1910.119, Lock-out/Tag-out (LOTO)1910.147, and Hot Work 190.252.

The proposed reintroduced legislation fails to address in the "findings" the importance of training, education, outreach, inspections, and enforcement at the local jurisdictional level with the I-Codes such as the International Building Code and International Fire Code which reference the NFPA combustible dust standards. There exponentially  more local building and fire inspectors conducting plan review, permit approval, and inspections than the limited resources of OSHA inspectors working out of distant area offices. Fires can never be effectively regulated at the federal level since fire prevention and protection is a local issue. A cohesive collaboration between local, state, and federal agencies would be a equitable solution in addressing the contentious and complex subject of combustible dust fire and explosion hazards in H-2 High-Hazard occupancies which appear to many as benign deflagration hazards with the continued occurrence of "near misses" throughout all sectors

YouTube video on slide #2 is Representative George Miller (D), Chairman of the Education and Labor Committee, making a statement during floor debate on HR 5522, the Worker Protection Against Combustible Dust Explosions and Fires Act, on April 30, 2008. The bill passed in the House of Representatives April 30, 2008, 6:56 p.m. with a 247/165 simple majority vote but was never passed by the Senate.

Saturday, March 23, 2013

OSHA Fire Prevention Plans (FPP) & Hazard Assessments Ignored by Many

Figure 6. Number of Combustible Dust Related Violations

Figure 6. "Number of Combustible Dust Related Violations" OSHA Status Report on Combustible Dust National Emphasis Program (NEP) does not even note any combustible dust related violations for "1910.39 Fire prevention plans." How odd especially with requirements of a written plan on proper handling and storage procedures for hazardous materials, potential ignition sources and their control, and the type of fire protection equipment necessary to control each major hazard. In addition to procedures to control accumulations of flammable and combustible waste materials in conjunction with procedures for regular maintenance of safeguards installed on heat-producing equipment to prevent the accidental ignition of combustible materials.” I guess combustible dust is not considered a combustible waste material nor a hazardous material?

Congressional Proposed Interim Standard
Since OSHA 1910.39 Fire prevention plans have been ignored regarding combustible dust hazards they will now be included in the reintroduced combustible dust legislation "Worker Protection Against Combustible Dust Explosions and Fires Act of 2013," for an OSHA interim combustible dust standard. Elements in an interim standard will include:

(2)written program that includes provisions for hazardous dust inspection, testing, hot work, ignition control, and housekeeping, including the frequency and method or methods used to minimize accumulations of combustible dust on ledges, floors, equipment, and other exposed surfaces.

(3) Requirements for engineering controls, administrative controls, and operating procedures, including means to control fugitive dust emissions and ignition sources, and the safe use and maintenance of process equipment and dust collection systems and filters.

(4) Requirements for workplace inspection and housekeeping to prevent accumulation of combustible dust in places of employment in such depths that it can present explosion, deflagration, or other fire hazards, including safe methods of dust removal.

(6) Requirements to provide written safety and health information and annual training to managers and employees and their representatives, including housekeeping procedures, hot work procedures, preventive, predictive, and periodic maintenance procedures, common ignition sources, and lock-out, tag-out procedure.

NOTE: OSHA Fire Prevention Plans (FPP) only required if all of your employees evacuate immediately during a fire emergency (page 15 .pdf) or if one of these three host standards apply: CFR 1910.1047(h)(1)(iii): Ethylene Oxide, CFR 1910.1050(d)(1)(iii): Methylenedianiline, or CFR 1910.1051(j): 1,3-Butadiene.

Additionally no mention in the 2009 OSHA Status Report on Combustible Dust National Emphasis Program regarding combustible dust related violations in failure to have a certified written Hazard assessment 1910.132(d)(1) “The employer shall assess the workplace to determine if hazards are present, or are likely to be present...” Legislators did not forget that one either in the reintroduced combustible dust legislation with (1) Requirements for hazard assessment to identify, evaluate, and control combustible dust hazards.

OSHA Citations: Fire Prevention Plans (FPP) and Certified Hazard Assessments
Question is how can there be hundreds of combustible dust related incidents annually with over 500 in 2011 according  to a CDPI preliminary analysis of NFIRS data, if the required OSHA written Fire Prevention Plans (FPP) and certified Hazard Assessments plans are adhered to? Is it just a paper chase and stakeholders doing nothing more than filing the required written plans in the office file cabinet?

Federal OSHA citations for the period October 2011 through September 2012 in the Lumber And Wood Products industries, (Except Furniture) there was no Federal OSHA citations for 1910.39 - Fire prevention plans (FPP). With the over 500 ComDust related incidents in 2011 according to a preliminary NFIRS analysis, the Lumber And Wood Products industries experienced over 16% of the incidents. How can there be so many incidents yet in the same vein FPP is adhered to regarding regular maintenance of safeguards installed on heat-producing equipment to prevent the accidental ignition of combustible materials?

This observation is not meant to solely pick on the Lumber And Wood Products as there are dozens of other diverse industries handling combustible particulate solids. For example out of the over 12,700 Federal OSHA citations at 2,419 facilities in the manufacturing sector from October 2011 through September 2012, only two (2) Federal OSHA citations for 1910.39 - Fire prevention plans (FPP)  So the odds of receiving an OSHA citation for FPP in that time period was 0.016% out of the nearly 13,000 citations. 


Conclusion
The problem is intensified when viewing the OSHA website  on combustible dust hazards where, "Federal OSHA standards are mandatory; they include provisions that address certain aspects of combustible dust hazards. Some are industry-wide and others and industry-specific." No mention at all regarding certified written hazard assessment 1910.132(d)(1) nor any note of 1910.39 Fire prevention plans. Additionally, in the OSHA ComDust NEP  numerous OSHA CPL's listed in the reference section yet CPL 2-1.037, Compliance Policy for Emergency Action Plans and Fire Prevention Plans excluded. Wouldn't it be prudent for all global stakeholders to implement the protections of  hazard assessments and fire protection plans now instead of waiting for the results of proposed combustible dust legislation and regulations? 

Tuesday, March 12, 2013

Building Signage Communicating Hazards Will Save Lives

Truss Signage

International Fire Code (2012) Appendix J - Building Information Sign, provides excellent guidance in communicating high-hazard occupancies to fire crews responding to combustible dust related fires and explosions. Many fire departments are not aware of the inherent special risk of a HazMat nature when responding to these types of incidents. The situation is especially critical with lack of resources for many jurisdictions in conducting pre-site visits as outlined in NFPA 1620 Standard for Pre-Incident Planning.

Truss signage,” is an excellent example currently implemented in numerous jurisdictions throughout the nation in preventing injures and fatalities of fire-fighters due to truss system failures. Similar signage as referenced in the International Fire Code (2012) and NFPA 704 will effectively communicate hazards to fire departments responding to facility combustible dust related incidents.

“Fire Chief did not receive an MSDS sheet from facility until the next day. Fire Chief added that if he had the MSDS sheet at the time of the incident his tactical decisions would have been different.” –excerpt accident report. This example illustrates if High-Hazard H-2 occupancy signage was affixed to the outside of buildings, fire crews would know upon arriving at the fireground that deflagration hazards are present. NFPA 704 signage produces similar results. A flammable vapor cloud explosion (VCE) is not much different than the severity of a wood dust deflagration as both involve damaging pressures waves followed by slower moving flame fronts of destructive flammable gases.

 

Questions, Problems, Feedback? Please send email by clicking this link...Thanks

©Copyright 2008-2012. Combustible Dust Policy Institute
The information in http://dustexplosions.blogspot.com/ is not meant to be a substitute for the Code of Federal Regulations (CFR), Federal Register, and other OSHA documents, which should serve as the primary source of regulatory guidance. The information on this site should not be used in place of appropriate technical or legal advice related to your company's specific circumstances. Combustible Dust Policy Institute tries to provide quality information, but we make no claims, promises or guarantees about the accuracy, completeness, or adequacy of the information contained in or linked to this web site and its associated sites. Combustible Dust Policy Institute has no liability arising from or relating to the use, interpretation, or application of the information or its accuracy or inaccuracy. Copyright notice: All materials in this site are copyrighted by the Combustible Dust Policy Institute. No materials may be directly or indirectly published, posted to Internet and intranet distribution channels, broadcast, rewritten for broadcast or publication or redistributed in any medium without permission.